Fire Resistance of a RC Slab exposed to a Parametric Fire Curve

In this article, we will analyse the fire resistance of a reinforced concrete slab exposed to a parametric fire curve. We will use the Eurocode as reference in this example.

Fire resistance is the ability of a structural system, a part of it, or an individual element to fulfil its required functions (such as load-bearing capacity and/or compartmentation/enclosing functions) for a specified fire exposure and for a specified period of time.

When exposed to the standard fire exposure (i.e., ISO 834), the term standard fire resistance is used.

The standard fire resistance of a reinforced concrete slab is defined by the R, E, I classification.

  • R is the load-bearing capacity, which is the ability to withstand mechanical loads without collapsing.

  • E is for integrity, which is the ability to prevent the passage of flames and hot gases through cracks or openings.

  • I is the insulation, which is the ability to limit temperature rise on the unexposed side (i.e., 140 K average or 180 K max limits).

The minimum slab thickness and reinforcement axis distance for each fire resistance class are shown in the following table assuming a simply-supported slab.

However, in this example the underside of the slab will be exposed to a parametric fire curve. A parametric fire curve is a time-temperature curve used to represent a realistic, post-flashover enclosure fire.

A parametric fire curve is governed by the following parameters:

  • Design fire load density based on expected quantity of combustible materials in the enclosure.

  • Opening factor based on the available openings (e.g., windows and doors) for ventilation.

  • Thermal inertia of bounding construction based on thermal properties of the walls, ceiling and floor.

Problem Definition and Assumptions

The slab arrangement and boundary conditions are illustrated in the diagram below.

Based on the physical arrangement and exposure conditions, the heat transfer process can be modelled as transient and one-dimensional under the following assumptions:

  • Radiation & Convection: Radiative and convective heat transfer uniformly across the fire and non-fire exposed surfaces of the concrete slab.

  • Exposure Condition: Parametric fire curve.

  • One-Dimensional Flow: Temperature gradients and heat flux ion the horizontal (x-axis) and depth (z-axis) directions are negligible.

  • Transient Problem: The system represents short-term heat transfer per unit area under fire exposure.

It is noted that the thermal properties of the concrete and reinforcement in reality will vary with temperature. However, in this example we will assume that thermal properties are constant irrespective of the temperature.

The .txt input file for the HeatCond2D model is available for download here.

If you have any queries or feedback regarding this article, please contact us.

Parametric Fire Curve Calculation (EN 1991-1-2 Annex A)

Summary of the parametric fire curve calculation is shown in the following table.

1. Governing Equation (Heating Phase)

According to Eurocode 1 (EN 1991-1-2, Annex A), the gas temperature during the heating phase (t ≤ tmax) is expressed as:

Tfire = 20 + 1325 [1 − 0.324exp(−0.2t*) − 0.204exp(−1.7t*) − 0.472exp(−19t*)]

where:

·       t* = t · Γ is the fictitious time (hours)

·       t is the real time (hours)

·       Γ is the dimensionless time factor

2. Enclosure Geometry & Opening Factor (fv)

Assuming a 6-sided rectangular enclosure with the following dimensions:

·       Enclosure width (W) = 6.0 m

·       Enclosure length (L) = 8.0 m

·       Enclosure height (H) = 2.8 m

Total Enclosure Surface Area (At):

At = 2[(W × L) + (W + L) × H] = 2[(6.0 × 8.0) + (6.0 + 8.0) × 2.8] = 174.4 m²

Total Vertical Opening Area (Av):

Assuming total openings equal to 20% of the floor area:

Av = 0.20 × (6.0 × 8.0) = 9.6 m²

Opening Factor (fv):

Assuming a weighted average opening height across all walls of heq = 1.4 m (valid within 0.02 ≤ fv ≤ 0.20 m⁰·⁵):

fv = (Av / At) · (heq)0.5 = (9.6 / 174.4) × (1.4)0.5 = 0.065 m⁰·⁵

3. Thermal Inertia (b) & Time Factor (Γ)

The thermal absorptivity of the enclosure boundary is defined as b = (ρ · c · k)0.5 (where ρ is density, c is specific heat, and k is thermal conductivity), subject to 100 ≤ b ≤ 2200 J/m²s1/2K.

For this calculation, assume b = 1000 J/m²s⁰·⁵K.

Γ = (fv / b)² / (0.04 / 1160)² = (0.065 / 1000)² / (0.04 / 1160)² = 3.553

4. Design Fire Load Density (qtd) & Heating Duration (tmax)

Based a residential design fire load density per unit floor area of qfd = 870 MJ/m², the design fire load density related to the total surface area At is:

qtd = (qfd × Af) / At = (870 × 6.0 × 8.0) / 174.4 = 239.5 MJ/m²

For residential fires with a medium fire growth rate, tlim = 20 minutes = 0.33 hours.

tmax = max(0.0002 · qtd / fv, tlim) = max(0.0002 × 239.5 / 0.065, 0.33) = max(0.7369, 0.33) = 0.7369 hours

t*max = tmax · Γ = 0.7369 × 3.553225 = 2.6185 hours

5. Maximum Gas Temperature (Tfire,max)

Substituting t*max = 2.6185 hours into the heating phase equation:

Tfire,max = 20 + 1325 (1 − 0.324e−0.2(2.6185) − 0.204e−1.7(2.6185) − 0.472e−19(2.6185))

= 1087.9 °C

6. Cooling Phase & Total Burn Duration

Since t*max = 2.6185 hours ≥ 2.0 hours, the linear cooling phase temperature is governed by:

Tfire = Tfire,max − 250(t* − t*max · x)

Because tmax = 0.7369 hours > tlim = 0.33 hours (ventilation-controlled fire), x = 1.0.

Solving for the time when gas temperature returns to ambient (Tfire = 20 °C):

20 = 1087.9 − 250(t* − 2.6185)   ⇒   t* = 2.6185 + (1087.9 − 20) / 250 = 6.890 hours

t_total = t* / Γ = 6.890 / 3.553225 = 1.939 hours (6980 seconds)

Therefore, a total simulation time of 7200 seconds (2.0 hours) is adopted to capture the complete heating and cooling cycle (i.e., total burn time).

Step-by-Step Heat Transfer Analysis

We will start by creating the reinforced concrete slab section.

Open the HeatCond2D app and tap on the Section Page. Ensure that <Geometry> is selected.

Section Page

Tap <Geometry>

Tap <Solid> to ensure that the Solid Element is selected. The Solid Element will represent the concrete slab

Next, tap the Section Template button to access the Section Template Page.

Section Page

Tap <Solid>

Tap Section Template button

On the Section Template Page, tap the Rectangular Section button to access the template for a rectangular section.

Section Template Page

Tap Rectangular Section button

Under Input Unit, select mm to change the unit.

Then, enter the following dimensions:

  • b0 = 200 in mm

  • d0 = 100 in mm

  • leave b1 and d1 empty.

Ensure that the Outer Element and Inner Element are set to Solid and Void1 respectively.

Rectangular Section Template

Change unit and enter dimensions

Tap the Scribble button to create the rectangular section.

Back on the Section Page, tap <Mat2> which will represent the reinforcement bar.

Section Page

Tap <Mat2>

Tap on the Shape Template button to access the Shape Template Page.

Tap <Circle> and enter the following dimensions:

  • cx = 100 in mm

  • cy = 30 in mm

  • r0 = 5 in mm

  • leave t, α and β empty.

Section Template

Tap <Circle>

Enter dimensions

Tap <Create> to create the shape and return to the Section Page.

Next, we will create the heat transfer model. On the Section Page, toggle on the Thermal toggle button to access the Thermal Page.

We will then generate the meshes for the model. Tap on the Mesh Properties button to access the Mesh Properties Page.

Section Page →Thermal Page

Tap <Thermal>

Tap Mesh Properties button

We will use symmetry modelling for this example.

On the Mesh Properties Page, tap on the Symmetry button to access the Symmetry Modelling Page.

Mesh Properties Page

Tap Symmetry button

On the Symmetry Modelling Page, tap the ‘NorthWest Corner’ and ‘SouthWest Corner’ buttons.

Symmetry Modelling

Tap NorthWest and SouthWest buttons

Tap the OK button to return to the Mesh Properties Page.

On the Mesh Properties Page, tap the Mesh Size button to access the Mesh Size Page.

Mesh Properties Page

Tap Mesh Size button

Enter Δx of 5 in mm and Δy of 5 in mm. Leave Mesh Symmetry as “About y- and x- axes and Selected Mesh Size as “Modified Mesh Size”.

Mesh Size Page

Enter mesh sizes

Tap the Generate button to return to the Mesh Properties Page.

On the Mesh Properties Page, select <Solid> and select <Concrete> under library. The pre-defined concrete thermal properties will be applied to the concrete slab.

Mesh Properties Page

Under <Solid>, select <Concrete> under library

Next, change the following thermal properties for the concrete material:

  • εm: 0.7

  • k: 1.0 in W/m.K

  • cp: 1000 in J/kg.K

Mesh Properties Page

Change thermal properties for Solid

Then, select <Mat2> and select <Steel> under library. The pre-defined steel thermal properties will be applied to the reinforcement bar.

Mesh Properties Page

Under <Mat2>, select <Steel> under library

Next, change the following thermal properties for the steel material:

  • εm: 0.7

  • k: 45 in W/m.K

Mesh Properties Page

Change thermal properties for Mat2

Tap the OK button to return to the Thermal Page.

We will then apply the boundary conditions to the model. On the Thermal Page, toggle off <Pick (Single)>.

Thermal Page

Toggle off <Pick (Single)>

Next, select a bottom node of the model.

Thermal Page

Tap a bottom node

Then, tap the <Select> button which will bring up a dialog box to confirm if selection is to include end nodes. Tap the Yes button to include the end nodes.

Thermal Page

Tap <Select>

Tap <Yes> to include end nodes

All the bottom nodes on the same plane as the selected node will be highlighted. Next, tap on the Boundary Condition button to access the Node Boundary Conditions Page.

Thermal Page

Tap Boundary Condition button

On the Node Boundary Conditions Page,

  • Under Exposure Type: Select <Exposure Temp.>

  • Under Temp. Type: Select <Profile Temp.>

Tap ‘Radiation Gain* (Transient only)’.

Node Boundary Conditions Page

Select <Exposure Temp.>

Select <Profile Temp.>

Tap ‘Radiation Gain* (Transient only’

Enter a View Factor of 1 and Emissivity of 1.0. Then, tap the OK button.

Node Boundary Conditions Page

Enter values for View Factor and Emissivity

Next, tap ‘Convective (Transient Gain/SteadyState)’.

Node Boundary Conditions Page

Tap ‘Convective (Transient only/SteadyState)’

Enter a Convective Heat Coefficient of 35 W/m².K. Then, tap the OK button.

Node Boundary Conditions Page

Enter value for Convective Heat Coefficient

Tap the OK button the apply the boundary condition and return to the Thermal Page.

On the Thermal Page, select a top node on the model.

Thermal Page

Tap a top node

Then, tap the <Select> button which will bring up a dialog box to confirm if selection is to include end nodes. Tap the Yes button to include the end nodes.

Thermal Page

Tap <Select>

Tap <Yes> to include end nodes

All the bottom nodes on the same plane as the selected node will be highlighted. Next, tap on the Boundary Condition button to access the Node Boundary Conditions Page.

Thermal Page

Tap Boundary Condition button

On the Node Boundary Conditions Page,

  • Under Exposure Type: Select <Exposure Temp.>

  • Under Temp. Type: Select <Constant Temp.>

Tap ‘Radiation Loss* (Transient only)’.

Node Boundary Conditions Page

Select <Exposure Temp.>

Select <Constant Temp.>

Tap ‘Radiation Loss* (Transient only)’

Enter a View Factor of 1 and Emissivity of 1.0. Then, tap the OK button.

Node Boundary Conditions Page

Enter values for View Factor and Emissivity

Next, tap ‘Conv. Loss* (Transient only)’.

Node Boundary Conditions Page

Tap ‘Conv. Loss* (Transient only)’

Enter a Convective Heat Coefficient of 4 W/m².K. Then, tap the OK button.

Node Boundary Conditions Page

Enter value for Convective Heat Coefficient

Then, enter a constant temperature of 20°C under each of the Radiation and Convective parts.

Node Boundary Conditions Page

Enter values for Constant Temperatures

Tap the OK button the apply the boundary condition and return to the Thermal Page. Tap <Clear> to clear the node selection on the Thermal Page.

Note that the external nodes with boundary condition applied will be marked.

Thermal Page

Tap <Clear>

On the Thermal Page, to view the boundary condition applied to a node, tap on the node.

Thermal Page

Tap a node to view node data

Next, we will specify the profile temperature for the fire. On the Thermal Page, tap the Profile button to access the Exposure Source Page.

Thermal Page

Tap Profile button

On the Exposure Source Page, tap the Exposure Temperature button to access the Exposure Temperature Page.

Exposure Source Page

Tap Exposure Temperature button

On the Exposure Temperature Page, tap <Expr> to access the Temperature Expression Page.

Exposure Temperature Page

Tap <Expr>

On the Temperature Expression Page, enter the expression for the Parametric Fire Curve in the Temperature Expression field.

The expression for the Parametric Fire Curve is expressed as:

max(min(20 + 1325*(1 - 0.324*exp(-0.2*t@h*[(fv/0.04)^2/(b/1160)^2]) - 0.204*exp(-1.7*t@h*[(fv/0.04)^2/(b/1160)^2]) - 0.472*exp(-19*t@h*[(fv/0.04)^2/(b/1160)^2])), 20 + 1325*(1 - 0.324*exp(-0.2*max(0.0002*qtd /fv,20/60)*[(fv/0.04)^2/(b/1160)^2]) - 0.204*exp(-1.7*max(0.0002* qtd /fv,20/60)*[(fv/0.04)^2/(b/1160)^2]) - 0.472* exp(-19*max(0.0002*qtd/fv,20/60)*[(fv/0.04)^2/(b/1160)^2]))) - [(fv/0.04)^2/(b/1160)^2]*(625 + max(((250-625)*(2-0.5)) *max((max(0.0002*qtd /fv,20/60)-0.5),0),250-625))*max(t@h-max(0.0002*qtd /fv,20/60),0),20) : fv=0.065 <ventilation factor> : b=1000.0 <thermal inertia> : qtd =239.5 <fire load energy density per total surface area>

Tap the OK button to return to the Exposure Temperature Page.

Temperature Expression Page

Enter Parametric Fire Curve expression in the Temperature Expression field

[Tips & Tricks: The peak temperature for the parametric fire curve expression occurs at time of 44.2 minutes or 2652 seconds. As the plot time interval is 15 seconds, the peak temperature calculated will be slightly lower than the peak temperature for the parametric fire curve but the temperature difference in this case is negligible.

But for other fire curves, check if the time interval is acceptable in addition to the simulation time step in the Simulation Data Page.]

On the Exposure Temperature Page, tap <Plot> to plot the expression.

Exposure Temperature Page

Tap <Plot> to plot expression

Tap the OK button when a dialog box appears requesting for confirmation to continue with the plotting.

Exposure Temperature Page

Tap <OK> to continue plotting

Tap the Close button to return to the Exposure Source Page.

Exposure Temperature Page

Tap <Close>

On the Exposure Source Page, tap the Close button to return to the Thermal Page.

Exposure Source Page

Tap <Close>

On the Thermal Page, tap the Simulation Data button to access the Simulation Data Page.

Thermal Page

Tap Simulation Data button

On the Simulation Data Page, under Solver, select Transient.

Enter a run time of 7,200 seconds based on the total burn time and Δt of 0.5 second. When using the transient solver, check that under each material (i.e., S1 for Solid, M2 for Mat2) that there are no red ticks under the Stability Check.

[Tips & Tricks: In addition to selecting a suitable time step to meet the Stability Check, the time step should capture the peak temperature or factor of the Fire Exposure Profile if ‘Profile Temperature’ is applied as the boundary condition.]

Simulation Data Page

Enter Run Time and Time Step

Tap the OK button to apply the simulation data and return to the Thermal Page.

On the Thermal Page, tap the Run button to run the heat transfer analysis.

Thermal Page

Tap Run button

A dialog box will appear. Tap the OK button to continue with the analysis.

Thermal Page

Tap <OK> to run analysis when dialog box appears

The Results Page will automatically appear after the analysis has been completed.

Results Page

Observe results

Tap on the node at the center of the reinforcement bar at coordinates (100 mm, 30 mm). Tap the time-history button (with ‘1’ showing) to view the time-history for that node.

Results Page

Tap node

Tap Time-History button

On the Time History Plot Page, tap the Add button and tap close to return to the Results Page.

Time History Plot Page

Tap <Add>

Back on the Results Page, tap on the top node  of the model at x = 100, y = 100 mm. Tap the time-history button (with ‘1’ showing) to view the time-history for that node.

Results Page

Tap node

Tap Time-History button

On the Time History Plot Page, tap the Add button and tap close to return to the Results Page.

Time History Plot Page

Tap <Add>

To view the Time History Plots for all the selected nodes, unselect any node on the Results Page.

Tap the time-history button (without ‘1’ showing).

Results Page

Unselect any selected node

Tap Time-History button

On the Time-History Plot Page, tap <Select All>.

Time History Plot Page

Tap <Select All>

Tap Node ID RadProf and ConvProf to select these two time-history plots and double tap ‘x (mm)’ to change the plot time unit to minutes.

[Tips & Tricks: Double tap the following to change the unit for time, ‘Node ID’: second, ‘x (mm): minute’, ‘y (mm): hour‘]

Time History Plot Page

Double tap x (mm) to change time unit to ‘minute’

Tap a point on the Node ID 0-20 plot where the temperature is not greater than 160°C. Tap the Close button to return to the Results Page.

Time History Plot Page

Tap a point

Tap on a point on the Node ID 14-20 at the peak temperature. Tap the Close button to return to the Results Page.

Time History Plot

Tap a point

Based on the time-history plots, the following temperatures at these times are shown.

  • Concrete temperature at coordinates (100 mm, y = 100 mm) at 79 minutes: 159.57°C (Node ID 0-20)

  • Reinforcement bar temperature at coordinates (100 mm, 30 mm) at 67 minutes: 522.9°C (Node ID 14-20)

The peak reinforcement bar temperature is 522.9°C for the duration of the parametric fire exposure, which is typically acceptable as the reinforcement bar limiting temperature is typically between 500°C to 600°C depending on the action that the slab is required to carry under a fire scenario. In this case, it is assumed that the slab will be designed with the reinforcement bar limiting being 523°C or greater.

In addition, the non-fire exposed side of the top of the slab is up to 159.6°C at 67 minutes of the parametric fire curve exposure (given the initial slab temperature is 20°C), which is less than the maximum average temperature rise for insulation of 140°C.

Therefore, the fire resistance of the slab is governed by its insulation criterion of up to 67 minutes when exposed to the parametric fire curve.

For a standard fire curve exposure, the Eurocode prescribes that this slab would be able to withstand up to 90 minutes of standard fire exposure.

The development of the ISO 834 and parametric fire curves is different and therefore the fire resistance in terms of time for the reinforced concrete slab is dependent on the type of fire exposure.

Fire Curves

Parametric & ISO 834

Note that this heat analysis is only an example and must not be applied to actual design with similar slab and reinforcement arrangement without review and approval of a qualified structural and fire engineer.